DC Circuit Breakerding Clip
- Brand:LS SOLAR
- Herkunft des Produkts: CHINA
- Compliance with standards: multi standard IEC 60947-2, EN60947-2, GB 14048.2
The JB is a DC circuit breaker dedicated to multi string photovoltaic installations.
JB is not polarity sensitive: (+) and (-) wires can inversed without any risk.
Compliance with standards: multi standard IEC 60947-2, EN60947-2, GB 14048.2
Technical Data:
Combined with a switch , the JB will be installed in a string PV protection enclosure at the end of each string of photovoltaic modules.
It can be locked (by a padlocking device) in OFF position as a safety measure for removal of the PV inverter.
Since a fault current can flow in the reverse direction to the operating current, the JB can detect and protect against any bidirectional current.
Main characteristics | ||
Rated service breaking capacity (Ics) | 100 % of the Icu | |
Endurance (O-C) | Electrical | 1,500 cycles (where L/R=2 ms) |
Mechanical | 20,000 cycles | |
Mechanical | 20,000 cycles | |
Degree of pollution | 2 | |
Category | A (no delay in accordance with IEC / EN 60947-2 standards) | |
Degree of protection Device in modular (IEC 60529) enclosure | IP40 | |
Tropicalisation | Relative humidity: 95 % at 55°C in accordance with IEC 60068-2 and GB 14048.2 standards | |
Temperature | Operating | -25°C to 70 °C |
Storage | -40°C to 85°C |
Precautions
To ensure the safety of the installation, it is necessary, depending on the various types of application, to combine the JB with:
- a residual current device at the AC end,
- a fault passage detector (insulation monitoring device) at the DC end
- an earth protection circuit breaker at the DC end
In all cases, fast action on site will be required to clear the fault (protection not ensured in the event of a double fault).
Main characteristics | |
Operating voltage (Ue) | 1P=250 V DC, 2P=500 V DC 3P=750 V DC, 4P=1000 V DC |
Rated insulation voltage (Ui) | 1,000 V DC |
Breaking capacity (Icu) | 10 kA |
Impulse voltage (Uimp) | 4 kV |
Electrical connection | By the bottom for In and Out |
Number of poles | 1P, 2P, 3P, 4P |
Standards | IEC 60947-2 EN 60947-2 |